A power system with two generators is shown in the figure below. The system (generators, buses and transmission lines) is protected by six overcurrent relays R ₁ to R ₆. Assuming a mix of directional and non-directional relays at appropriate locations, the remote backup relays for R ₄ are
A single-phase transformer of rating 25 kVA, supplies a 12 kW load at power factor of 0.6 lagging. The additional load at unity power factor in kW (round off to two decimal places) that may be added before this transformer exceeds its rated kVA is __________.